# Modbus Input Plugin
|
|
|
|
The Modbus plugin collects Discrete Inputs, Coils, Input Registers and Holding
|
|
Registers via Modbus TCP or Modbus RTU/ASCII.
|
|
|
|
### Configuration
|
|
|
|
```toml
|
|
[[inputs.modbus]]
|
|
## Connection Configuration
|
|
##
|
|
## The module supports connections to PLCs via MODBUS/TCP or
|
|
## via serial line communication in binary (RTU) or readable (ASCII) encoding
|
|
##
|
|
## Device name
|
|
name = "Device"
|
|
|
|
## Slave ID - addresses a MODBUS device on the bus
|
|
## Range: 0 - 255 [0 = broadcast; 248 - 255 = reserved]
|
|
slave_id = 1
|
|
|
|
## Timeout for each request
|
|
timeout = "1s"
|
|
|
|
## Maximum number of retries and the time to wait between retries
|
|
## when a slave-device is busy.
|
|
# busy_retries = 0
|
|
# busy_retries_wait = "100ms"
|
|
|
|
# TCP - connect via Modbus/TCP
|
|
controller = "tcp://localhost:502"
|
|
|
|
## Serial (RS485; RS232)
|
|
# controller = "file:///dev/ttyUSB0"
|
|
# baud_rate = 9600
|
|
# data_bits = 8
|
|
# parity = "N"
|
|
# stop_bits = 1
|
|
# transmission_mode = "RTU"
|
|
|
|
|
|
## Measurements
|
|
##
|
|
|
|
## Digital Variables, Discrete Inputs and Coils
|
|
## name - the variable name
|
|
## address - variable address
|
|
|
|
discrete_inputs = [
|
|
{ name = "Start", address = [0]},
|
|
{ name = "Stop", address = [1]},
|
|
{ name = "Reset", address = [2]},
|
|
{ name = "EmergencyStop", address = [3]},
|
|
]
|
|
coils = [
|
|
{ name = "Motor1-Run", address = [0]},
|
|
{ name = "Motor1-Jog", address = [1]},
|
|
{ name = "Motor1-Stop", address = [2]},
|
|
]
|
|
|
|
## Analog Variables, Input Registers and Holding Registers
|
|
## measurement - the (optional) measurement name, defaults to "modbus"
|
|
## name - the variable name
|
|
## byte_order - the ordering of bytes
|
|
## |---AB, ABCD - Big Endian
|
|
## |---BA, DCBA - Little Endian
|
|
## |---BADC - Mid-Big Endian
|
|
## |---CDAB - Mid-Little Endian
|
|
## data_type - INT16, UINT16, INT32, UINT32, INT64, UINT64, FLOAT32, FLOAT32-IEEE (the IEEE 754 binary representation)
|
|
## scale - the final numeric variable representation
|
|
## address - variable address
|
|
|
|
holding_registers = [
|
|
{ name = "PowerFactor", byte_order = "AB", data_type = "FLOAT32", scale=0.01, address = [8]},
|
|
{ name = "Voltage", byte_order = "AB", data_type = "FLOAT32", scale=0.1, address = [0]},
|
|
{ name = "Energy", byte_order = "ABCD", data_type = "FLOAT32", scale=0.001, address = [5,6]},
|
|
{ name = "Current", byte_order = "ABCD", data_type = "FLOAT32", scale=0.001, address = [1,2]},
|
|
{ name = "Frequency", byte_order = "AB", data_type = "FLOAT32", scale=0.1, address = [7]},
|
|
{ name = "Power", byte_order = "ABCD", data_type = "FLOAT32", scale=0.1, address = [3,4]},
|
|
]
|
|
input_registers = [
|
|
{ name = "TankLevel", byte_order = "AB", data_type = "INT16", scale=1.0, address = [0]},
|
|
{ name = "TankPH", byte_order = "AB", data_type = "INT16", scale=1.0, address = [1]},
|
|
{ name = "Pump1-Speed", byte_order = "ABCD", data_type = "INT32", scale=1.0, address = [3,4]},
|
|
]
|
|
```
|
|
|
|
### Metrics
|
|
|
|
Metric are custom and configured using the `discrete_inputs`, `coils`,
|
|
`holding_register` and `input_registers` options.
|
|
|
|
|
|
### Example Output
|
|
|
|
```
|
|
$ ./telegraf -config telegraf.conf -input-filter modbus -test
|
|
modbus.InputRegisters,host=orangepizero Current=0,Energy=0,Frecuency=60,Power=0,PowerFactor=0,Voltage=123.9000015258789 1554079521000000000
|
|
```
|